Siemens Type AC-schakelaar J3TF
Specificatie
Type | J3TF-9/12 | J3TF-16/22 | J3TF-32 | J3TF-45/63 | J3TF-75/85 | J3TF-110/140 | J3TF-170/205 | J3TF-250/300 | J3TF-400/475 | |
Mechanisch Uithoudingsvermogen(X106) | 10 | 10 | 10 | 8 | 8 | 8 | 8 | 8 | 8 | |
Conventioneel thermische stroom (A) | 20 | 30 | 45 | 80 | 100 | 160 | 210 | 300 | 400/550 | |
Nominale isolatie spanning (V) | 660 | 660 | 660 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | |
Geschat operationeel stroom(A) | AC-3 | 9/12 | 16/22 | 32 | 45/63 | 75/85 | 110/140 | 170/205 | 250/300 | 400/475 |
AC-4 | 3,3/4,3 | 7,7/8,5 | 15.6 | 24/28 | 34/42 | 54/68 | 75/96 | 110/125 | 150 | |
Vermogen van regelbare motor (KW) AC-3 | 380V | 4/5,5 | 7,5/11 | 15 | 22/30 | 37/45 | 55/75 | 90/110 | 132/160 | 200/250 |
660V | 5,5/7,5 | 11 | 23 | 39/55 | 67 | 100 | 156 | 235 | 375 | |
Vermogen van regelbare motor (KW) AC-4 | 380V | 1,4/1,9 | 3,5/4 | 7.5 | 12/14 | 17/21 | 27/35 | 38/50 | 58/66 | 81 |
660V | 2,4/3,3 | 6/6,6 | 13 | 20,8/24 | 29,5/36 | 46,9/60 | 66/86 | 100/114 | 140 | |
Frequentie van gebruik (ik/u) | AC-3 | 1000 | 750 | 750 | 1200/1000 | 1000/850 | 1000/750 | 700/500 | 700/500 | 500/420 |
AC-4 | 250 | 250 | 250 | 400/300 | 300/250 | 300/200 | 200/130 | 200/130 | 150 | |
Elektrisch uithoudingsvermogen (X106) | AC-3 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 |
AC-4 | 0,2 | 0,2 | 0,2 | 0,2 | 0,2 | 0,2 | 0,2 | 0,2 | 0,2 | |
Werkspanning bereik van spoel | (0,8-1,1)Ue | |||||||||
Stroom verbruik van spoel | Aantrekkelijk (VA) | 10 | 10 | 12.1 | 17 | 32 | 39 | 58 | 84 | 115 |
Beginnend (VA) | 68 | 69 | 101 | 183 | 330 | 550 | 910 | 1430 | 2450 | |
Nominale isolatiespanning van hulpcontacten (V) | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 |
Conventionele thermische stroomvan hulpcontacten(A) | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 |
Nominale bedrijfsstroomvan hulpcontacten(A) | AC15 380/220 | 6/10 | 6/10 | 4/6 | 4/6 | 4/6 | 4/6 | 4/6 | 4/6 | 4/6 |
DC13 220v | 0,45 | 0,45 | 0,45 | 0,45 | 0,45 | 0,45 | 0,45 | 0,45 | 0,45 | |
Nominale spanning van de controle spoel (V) | 50 Hz | 24 36 48 110 127 220 380, enz. | ||||||||
60 Hz | 24 110 220 440 enz |
Toepassingsscenario's:
Meestal geïnstalleerd in de verdeelkast op de vloer, computercentrum, telecommunicatieruimte, liftcontrolekamer, kabel-tv-kamer, gebouwcontrolekamer, brandweercentrum, industriële automatische controleruimte, ziekenhuisoperatiekamer, bewakingskamer en verdeelkastapparatuur met elektronisch medisch apparaat .
Schrijf hier uw bericht en stuur het naar ons